SWMS template · Plumbing & Gas

Gas Leak Detection and Repair — Safe Work Method Statement

Safe Work Method Statement for responding to reported gas leaks on consumer piping and appliances, covering making the area safe, isolating the supply, locating the leak by detector, leak solution and pressure test, repairing the fault, and re-testing and recommissioning.

Category
Plumbing & Gas
HRCW
2 categories
Job steps
7
Hazards rated
17
PPE items
6

A gas leak call-out is High Risk Construction Work under the model WHS Regulations because you are working on pressurised gas piping and the area may already have a flammable atmosphere. A SWMS is required, and it has to be in place before the work starts, so keep a copy that covers this task in the vehicle rather than writing one on the doorstep.

The main hazard is ignition. Gas only needs a spark to ignite once it reaches a flammable concentration, and that spark can come from a light switch, a doorbell, a phone, a fridge compressor or a power tool. If there is a strong smell inside, get people out first, do not switch anything on or off, open doors and windows, and isolate at the meter or cylinder if it is safe to reach. Natural gas is lighter than air and collects in ceilings and high spaces. LPG is heavier than air and pools in subfloors, pits, cellars and low points, where it can sit for a long time. Subfloor work on an LPG leak needs gas testing before you go in.

Find leaks with a calibrated gas detector, leak detection solution and a pressure or tightness test with a manometer. Never use a flame. If the leak is on the network side of the meter, at the meter or regulator, or in the street, it belongs to the gas distributor. Make the area safe and call the distributor's emergency line rather than working on their assets. Repairs that involve brazing copper are hot work, so the section must be isolated, purged and confirmed gas-free before any heat is applied.

Gas fitting is licensed work in every state and territory, and the licence class, compliance certificate and notification rules differ. Check your state or territory regulator. Work must meet AS/NZS 5601.1 and the appliance manufacturer's instructions. After any repair, re-test the whole installation for tightness, purge, relight every appliance and check for correct burner operation and flue spillage, because a leak repair can disturb other joints and appliances.

Customise this template with the gas type (natural gas or LPG), the meter or cylinder location and isolation valve, the area of the reported leak, the gas detector model and calibration date, the repair method (joint remake, section replacement, brazing), the tightness test pressure and duration you will use, the appliances to be recommissioned, and how you will report the work to the owner and regulator.

High Risk Construction Work Types

  • Work on or near pressurised gas distribution mains or piping
  • Work in an area that may have a contaminated or flammable atmosphere

Personal Protective Equipment

  • Calibrated combustible gas detector
  • Safety glasses
  • Leather gloves (heat-resistant for brazing)
  • Long-sleeve cotton or flame-resistant clothing
  • Steel-capped safety boots
  • Dry powder fire extinguisher (on hand)

Risk Assessment

RatingsCatastrophicHighModerateLow

Step 1Arrival, initial assessment and making the area safe

Hazard / RiskInitial RiskControl MeasuresResidual RiskResponsibility
Explosion from igniting accumulated gasCatastrophicCheck with the detector from the doorway before entering. If gas is detected inside or the smell is strong, evacuate occupants, do not operate switches, phones or doorbells in the area, remove ignition sources, and open doors and windows from the outside where possible.ModerateGas Fitter
Leak on the distributor's side of the meter or in the streetHighIf the leak is at the meter, regulator, service line or main, keep people clear, isolate at the meter if safe, and call the gas distributor's emergency line. Do not work on distributor assets.LowGas Fitter
Occupants returning or using appliances during the workModerateExplain the hazard to the occupant. Tag the isolation valve. Tell occupants not to relight or use any gas appliance until you hand back.LowGas Fitter

Step 2Isolating the gas supply

Hazard / RiskInitial RiskControl MeasuresResidual RiskResponsibility
Gas continuing to flow from a faulty or seized meter valveHighTurn off at the meter or cylinder valves and confirm isolation by watching the meter dial or by pressure test. If the valve will not close, call the distributor or LPG supplier and keep the area clear.LowGas Fitter
Someone turning the gas back on during the repairHighLock or tag the meter valve or cylinder valves with a danger tag naming the fitter and date. Only the fitter who applied the tag removes it.LowGas Fitter

Step 3Ventilating and gas testing the work area

Hazard / RiskInitial RiskControl MeasuresResidual RiskResponsibility
LPG pooled in subfloor, pit or low spaceHighTest at floor and low points before entry. Do not enter until readings are clear. Ventilate with doors, vents or an intrinsically safe or air-driven fan placed outside the gas zone. Treat restricted subfloors as confined spaces if they meet the definition.LowGas Fitter
Natural gas trapped in ceiling space or cupboardsHighTest at high points and inside cupboards. Open manholes and cupboards to vent. Keep testing while you work, not just at the start.LowGas Fitter

Step 4Locating the leak

Hazard / RiskInitial RiskControl MeasuresResidual RiskResponsibility
Ignition from using a flame or non-rated equipmentCatastrophicNever use a flame to find a leak. Use a calibrated gas detector and leak detection solution on joints. Bump test the detector before each job.LowGas Fitter
Missing a slow leak and leaving it unrepairedHighCarry out a pressure decay test on the isolated installation with a manometer. Isolate sections to narrow down the leak. Check appliance connections, flexible hoses and bayonet fittings, which are common leak points.LowGas Fitter
Back strain and trapped limbs in tight subfloorsModeratePlan the route in and out. Use knee pads and a torch rated for the area. A second person stays at the access point if the subfloor is restricted.LowGas Fitter

Step 5Repairing the leaking joint or section

Hazard / RiskInitial RiskControl MeasuresResidual RiskResponsibility
Fire when brazing on a pipe that still holds gasCatastrophicIsolate and purge the section to a safe location outdoors. Confirm gas-free with the detector at the work point before lighting the torch. Fire extinguisher within reach. Remove or shield combustibles.ModerateGas Fitter
Burns from torch and hot pipeModerateHeat-resistant gloves, safety glasses and long sleeves. Let joints cool before handling. Check for smouldering material for 30 minutes after hot work in roof or subfloor spaces.LowGas Fitter
Using unsuitable fittings or sealantsModerateUse only fittings, thread sealants and hoses certified for gas and the gas type. Replace damaged flexible connectors rather than repairing them.LowGas Fitter

Step 6Tightness testing and purging

Hazard / RiskInitial RiskControl MeasuresResidual RiskResponsibility
Remaining leak not found before gas is restoredHighTightness test the whole installation to AS/NZS 5601.1 and record the test pressure and duration. Do not restore supply until the test passes.LowGas Fitter
Purged gas building up in an enclosed areaHighPurge to outside air away from ignition sources, windows and openings. Monitor with the detector while purging.LowGas Fitter

Step 7Recommissioning appliances and handover

Hazard / RiskInitial RiskControl MeasuresResidual RiskResponsibility
Carbon monoxide from an appliance that is not burning correctlyHighRelight each appliance to the manufacturer's instructions. Check flame picture, operating pressure and flue spillage. Do not hand back an appliance that fails. Isolate and tag it and tell the owner in writing.LowGas Fitter
Owner unaware of what was found and fixedModerateExplain the fault and repair to the owner. Complete the compliance paperwork required in your state or territory. Remove the danger tag only after all checks pass.LowGas Fitter

Relevant Codes of Practice

Worker Acknowledgement

By signing below, I confirm that I have read, understood and agree to comply with this Safe Work Method Statement.

NameDateSignature
NameDateSignature
NameDateSignature
NameDateSignature
NameDateSignature
NameDateSignature
NameDateSignature
NameDateSignature

Get this template

Free. Edit the Excel version, or print the PDF and fill it in by hand.